Using terminal commands
REMARKS GET/SET. Not applicable to the A733GSM/GPRS.
R
EMOTE Yes, SET only.
E
XAMPLE FREQ 433925000 25000
9193 FREQ 0
#
FREQ
9193 FREQ 433925000 25000 0
#
RSSI
AVAILABLE FOR
A731 A733A732 A733GSM
v
DESCRIPTION Sets/returns the Relative Signal Strength Indicator threshold at which the RF
receiver must wake up.
PARAMETERS The threshold value. For the A73x non-GSM RTU, it can take values from 0 to 255;
it is typically factory set to 42.
R
ETURNS The instant RSSI value and the programmed threshold.
REMARKS GET/SET. Not applicable to the A733GSM/GPRS.
REMOTE No.
E
XAMPLE RSSI 42
9193 RSSI 0
#
RSSI
9193 RSSI 34 42 0
#
Note: The values of the RSSI threshold have no units, they are arbitrary. However, a
value of 160 corresponds approximately to the maximum value allowed in the
addVANTAGE software (that is, 8 µV).
ID
AVAILABLE FOR
A731 A733A732 A733GSM
D
ESCRIPTION Sets/returns the node’s ID.
P
ARAMETERS The node ID.
RETURNS The node ID.
R
EMARKS GET/SET.
R
EMOTE Yes, SET only.
E
XAMPLE ID 4557
9193 ID 0
#
ID
4557 ID 4557 0
#